This containerized battery energy storage system (BESS) system is a highly integrated energy storage solution based on lithium iron phosphate (LFP) technology. It utilizes 280Ah / 314Ah LFP battery cells. The air-cooled battery container capacity ranges from 1.5 to 3.35 MWh per unit, while the liquid-cooled version ranges from 2 to 5 MWh per unit. The energy storage system is equipped with an integrated PCS (power conversion system) and step-up transformer unit, meeting project requirements from 0.25C to 1C.
Large-scale centralized solar and wind power plants
Distributed solar and wind power generation
Power ancillary services
Peak-valley arbitrage
Power capacity expansion
| Battery Container | Total Energy Capacity (MWh) | 3.35 | 3.35 | 5.015 |
| Battery Cell Capacity (Ah) | 280 | 280 | 314 | |
| Cell Nominal Voltage (V) | 3.2 | 3.2 | 3.2 | |
| Module Configuration | IP16S | 1P52S | 1P52S | |
| Standard Charge/Discharge Current (A) | 140 | 140 | 157 | |
| Battery Cluster Configuration | 1P416S | 1P416S | 1P416S | |
| Cluster Nominal Energy (kWh) | 372.736 | 372.736 | 417.997 | |
| Voltage Range (V) | 1040-1518.4 | 1040-1518.4 | 1040-1518.4 | |
| System/Rack Configuration | 9P416S | 9P416S | 12P416S | |
| Thermal Management | Air Cooling | Liquid Cooling | Liquid Cooling | |
| Fire Suppression System | Perfluorohexanone, Container-level | Perfluorohexanone, Pack-level | Perfluorohexanone, Pack-level | |
| Container Size (ft) | 32 | 20 | 20 | |
| Weight (t) | 40 | 36 | 45 | |
| Integrated PCS & Step-up Unit | Rated Power (MW) | 3.45 | 3.45 | 5 |
| Transformer Capacity (MVA) | 3.45 | 3.45 | 5 |